ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
BODY HEIGHT | 2.359 INCHES NOMINAL |
BODY LENGTH | 2.844 INCHES NOMINAL |
BODY STYLE | SINGLE POLE TYPE |
BODY WIDTH | 0.969 INCHES NOMINAL |
BOSS HEIGHT | 0.187 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SINGLE LOCATION |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC SINGLE LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC SINGLE LOCATION |
MOUNTING FACILITY TYPE AND QUANTITY | 1 TERMINAL |
POLE QUANTITY | 1 |
RESET METHOD | MANUAL |
SPECIAL HANDLING FEATURE | MAGNETIC |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 2 BUS BAR |
TRIP RELEASE AMBIENT TEMP RATING | 40.0 CELSIUS NOMINAL SINGLE LOCATION |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS SINGLE LOCATION |
TRIP RELEASE METHOD | THERMAL-MAGNETIC SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
UNPACKAGED UNIT WEIGHT | 5.100 OUNCES NOMINAL |