ACTUATOR FUNCTION | RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
CASE MATERIAL | PLASTIC |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS |
OVERALL HEIGHT | 3.969 INCHES NOMINAL |
OVERALL LENGTH | 6.000 INCHES NOMINAL |
OVERALL WIDTH | 2.750 INCHES NOMINAL |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 150.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 2 UNTHREADED HOLE |
POLE QUANTITY | 2 |
RESET METHOD | MANUAL |
TERMINAL TYPE AND QUANTITY | 4 COMPRESSION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 70.000 MINIMUM AT 200 PCT ALL LOCATIONS |
TRIP RELEASE AMBIENT TEMP RATING | 40.0 CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 100.0 ALL LOCATIONS |
UNTHREADED MOUNTING HOLE DIAMETER | 0.344 INCHES NOMINAL |