Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
TQB213060969GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
BODY HEIGHT2.359 INCHES NOMINAL
BODY LENGTH3.281 INCHES NOMINAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH2.000 INCHES MAXIMUM
BOSS HEIGHT0.140 INCHES NOMINAL
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.000 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKED
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS
MANUAL ACTUATOR TYPE AND QUANTITY2 TOGGLE
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS5000.0 AC ALL LOCATIONS
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE30.0 AMPERES AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 TERMINAL
POLE QUANTITY2
RESET METHODMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY4 COMPRESSION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT18.000 MINIMUM AT 200 PCT AND 125.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING50.0 CELSIUS MAXIMUM ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
UNPACKAGED UNIT WEIGHT8.000 OUNCES NOMINAL