5360-00-153-4945 SPRING,HELICAL Index 5950-00-153-4964 TRANSFORMER,POWER

National Stock Number:
5925-00-153-4962

Federal Supply Class:
5925

National Item Identification Number:
001534962

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
12212300131795EATON CORPORATION
85-33019-0230554DEPARTMENT OF DEFENSE PROJECT MANAGER-MOBILE ELECTRIC POWER
TQC1105LL60969GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL
TQC1105WL60969GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL
TQC1110WL60969GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
BODY HEIGHT2.922 INCHES NOMINAL
BODY LENGTH3.875 INCHES NOMINAL
BODY STYLESINGLE POLE TYPE
BODY WIDTH1.000 INCHES NOMINAL
BOSS HEIGHT0.187 INCHES NOMINAL
CASE MATERIALPLASTIC
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ600.0 SINGLE LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC SINGLE LOCATION
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE10.0 AMPERES AC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS5000.0 AC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY2 TERMINAL
POLE QUANTITY1
RESET METHODMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY1 COMPRESSION AND 1 CLIP
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT15.000 MINIMUM AT 200 PCT AND 150.000 MAXIMUM AT 200 PCT SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING40.0 CELSIUS NOMINAL SINGLE LOCATION
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND TIME DELAY SINGLE LOCATION
TRIP RELEASE METHODTHERMAL-MAGNETIC SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 SINGLE LOCATION