ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
BODY LENGTH | 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
BODY WIDTH | 2.990 INCHES MINIMUM AND 3.010 INCHES MAXIMUM |
BOSS HEIGHT | 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, THREE, AND FOUR LINKED |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 50.0 OR 60.0 OR 400.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND VIBRATION RESISTANT |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SECOND LOCATION |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP THIRD LOCATION |
INTERNAL TRIP RELEASE CONFIGURATION | RELAY TRIP FOURTH LOCATION |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATION |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 4 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 60.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM |
NOMINAL THREAD SIZE | 0.138 INCHES |
POLE QUANTITY | 4 |
RESET METHOD | MANUAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
SWITCH CURRENT RATING AND TYPE IN AMPS | 10.0 AC |
SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 125.0 AC |
TERMINAL TYPE AND QUANTITY | 10 THREADED STUD |
THREAD PITCH DIAMETERS | +0.1177 TO 0.1214 INCHES |
THREAD QUANTITY PER INCH | 32 |
THREAD SERIES DESIGNATOR | UNC |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.200 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT FIRST LOCATION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.200 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT SECOND LOCATION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.200 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT THIRD LOCATION |
TRIP RELEASE CHARACTERISTIC | TIME DELAY FIRST LOCATION |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS FOURTH LOCATION |
TRIP RELEASE CHARACTERISTIC | TIME DELAY SECOND LOCATION |
TRIP RELEASE CHARACTERISTIC | TIME DELAY THIRD LOCATION |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 ALL LOCATIONS |