ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
BODY LENGTH | 2.203 INCHES NOMINAL |
BODY STYLE | SINGLE POLE TYPE |
BODY WIDTH | 0.766 INCHES MAXIMUM |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.438 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.812 INCHES NOMINAL |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 30.0 AC AND 30.0 DC SINGLE LOCATION |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC AND 100.0 AMPERES DC SINGLE LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 AC AND 2000.0 DC SINGLE LOCATION |
MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.406 INCHES NOMINAL |
NOMINAL THREAD SIZE | 0.164 INCHES |
POLE QUANTITY | 1 |
RESET METHOD | AUTOMATIC |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 122.0 SINGLE LOCATION |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 2 SCREW |
THREAD QUANTITY PER INCH | 32 |
THREAD SERIES DESIGNATOR | UNC |
TRIP RELEASE AMBIENT TEMP RATING | 25.0 CELSIUS NOMINAL SINGLE LOCATION |
TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
TRIP RELEASE METHOD | THERMAL SINGLE LOCATION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 30.000 NOMINAL AT 200 PCT SINGLE LOCATION |