ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
BODY LENGTH | 5.769 INCHES MINIMUM AND 5.831 INCHES MAXIMUM |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
BODY WIDTH | 2.041 INCHES MINIMUM AND 2.103 INCHES MAXIMUM |
BOSS HEIGHT | 0.209 INCHES MINIMUM AND 0.229 INCHES MAXIMUM |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.516 INCHES MINIMUM AND 3.578 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.016 INCHES MINIMUM AND 1.036 INCHES MAXIMUM |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CRITICALITY CODE JUSTIFICATION | FEAT |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.719 INCHES MINIMUM AND 2.781 INCHES MAXIMUM |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.016 INCHES MINIMUM AND 1.036 INCHES MAXIMUM |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
FRAGILITY FACTOR | MODERATELY RUGGED |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT AND SHOCK RESISTANT AND VIBRATION RESISTANT |
INTERNAL TRIP RELEASE CONFIGURATION | RELAY TRIP SECOND LOCATION |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 125.0 DC ALL LOCATIONS |
MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES DC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 DC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.172 INCHES MINIMUM AND 3.296 INCHES MAXIMUM |
NOMINAL THREAD SIZE | 0.138 INCHES |
POLE QUANTITY | 2 |
RESET METHOD | MANUAL |
SPECIAL FEATURES | COMMUNICATION CENTER,PATCHING NECESSARY TO WEAPONS SYSTEM |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
SWITCH CURRENT RATING AND TYPE IN AMPS | 5.0 AC |
SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 125.0 AC |
TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
THREAD QUANTITY PER INCH | 32 |
THREAD SERIES DESIGNATOR | UNC |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS SECOND LOCATION |
TRIP RELEASE CHARACTERISTIC | TIME DELAY FIRST LOCATION |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 30.000 MINIMUM AT 200 PCT AND 100.000 MAXIMUM AT 200 PCT FIRST LOCATION |